64 ECOM0010 - User manual
25
SEP
Proportional Band Multiplier
Word modbus 2025
LabSoftView:
1 .00..5.00 > Default: 1.00
Ex: 1 = 1
Modbus:
100..500 hundreths
Ex: 100 = 1.00
26
RXGE
Overlap/Dead Band
Dead band combination for heating / cooling PID
Word modbus 2026
LabSoftView:
-20.0..+50.0 % > Default: 0
Ex: 10 = 10 %
Modbus:
-200..+500 tenths of %
Ex: 100 = 10.0 %
Negative: Dead band
Positive: Overlapping
27
FRFW
Cooling Cycle Time
Cycle time for cooling output
Word modbus 2027
TFDPOETDefault: 10
28
DXPD
Aumatic / Manual
Enables the automatic/manual selection
Word modbus 2028
0 Disabled. > Default
1 Enabled
2 Enabled Stored
29
6/DG
Slave Address
Selects slave address for serial communication
Word modbus 2029
1..254. > Default: 240