54 ECOM0010 - User manual
controllers with the same address on the same line.
Address 255 can be used by the Master to communicate with
all the connected equipment (broadcast mode), while with
the address 0 all the devices receive the command, but no
response is expected.
ECOM0010 can introduce a delay (in milliseconds) of the
response to the master request. This delay must be set on
QBSBNFUFS
6HGH
Each parameter modication is saved by the controller in
the EEPROM memory (100000 writing cycles), while the
setpoints are saved with a delay of 10 seconds after the last
modication.
NB: Changes made to words that are dierent from those
reported in the following table can lead to malfunction.
Modbus RTU protocol features
Baud-rate
Selectable on parameter 
EGUW
Value : bit/s Value : bit/s
Value: bit/s Value : bit/s
Value : bit/s Value: bit/s
Value: bit/s Value :bit/s
Value: bit/s
Format
Selectable on parameter 
VSS
Value : N Value: N
Value: E Value : E
Value : O Value : O
Supported
functions
WORD READING (max  word) (HEXx, HEX x)
SINGLE WORD WRITING (HEX x)
MULTIPLE WORDS WRITING (max  word) (HEX x)
RO = Read Only R/W = Read/Write WO = Write Only