58 ECOM0010 - User manual
3
*FD
Gain Calibration AI1
Value in % to multiply with the displayed value and to add
to this displayed value to calibrate the process value
Word modbus 2003
LabSoftView:
-99.9..+99.9 % > Default: 0
E.g. : 10 = 10 %
Modbus:
-999..+999 tenths of %
E.g. : 10 = 1.0 %
The formula is: T
OUT
= T
IN
+ (T
IN
x Gain / 100)
T
IN
: Measure
T
OUT
: Displayed value
4
F+\
Command Hysteresis
Hysteresis on ON/OFF control or dead band in PID.
Word modbus 2004
LabSoftView:
-99.9..+99.9 degrees >
Default:0
E.g. : 10 = 10 °C / °F
Modbus:
-999..+999 tenths of
degrees
E.g. : 10 = 1.0 °C / °F
5
WXQH
Tune
Autotuning type selection.
Word modbus 2005
0 Disabled. > Default.
1 Automatic. Calculation of PID parameters at
starting and on control setpoint modication.
2 Manual. Launch by word modbus 1004.
4ZODISPOJ[FE
Comentarios a estos manuales