Celduc Temperature controller ECOM Manual de usuario Pagina 48

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 103
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 47
User manual - ECOM0010 49
in the system. At this point the autotuning is launched (value
JOXPSE&BDIDPOUSPMMFSDBMDVMBUFTUIFOFX1*%WBMVFT
When the procedure ends, it switches othe control output
and sets the value 4 in word 1004. The master, which keeps
reading the word 1004, checks the various zones and when all
of them have reached the value 4 it will bring to 0 the value
of word 1004.
The various devices will regulate the temperature based on
the new values.
N.B. The master must read the Word 1004 at least every 10
seconds otherwise the controller will automatically exit the
autotuning procedure.
6.4 Automatic / Manual control mode of the
percentage of the output
This function allows to select automatic or manual control of
the output percentage. With parameter 28 (
DXPD
word
2028), you can select two methods.
1. The rst selection (write 1 in word 2028) allows to modify,
through the word 1005, the functioning mode: after
writing 1 it is possible to change the output percentage on
word 1011 (range 0-10000).
To return to automatic mode, write 0 on word 1005.
2. The second selection (write 2 in word 2028) enables the
same mode, but with two important variants:
t *GUIFSFJTBUFNQPSBSZMBDLPGWPMUBHFPSBGUFSTXJUDIPò
the manual functioning will be maintained as well as the
previously set output percentage value.
t *G UIF TFOTPS CSFBLT EVSJOH BVUPNBUJD GVODUJPOJOH UIF
controller swithes to manual mode while maintaining the
output percentage control unchanged as generated by
the PID immediately before the break.
Vista de pagina 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 102 103

Comentarios a estos manuales

Sin comentarios