Celduc Temperature controller ECOM Manual de usuario Pagina 62

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 103
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 61
User manual - ECOM0010
21
DVH
Alarm 1 State Error
Contact status for alarm 1 output in case of error
Word modbus 2021
0 Open contact. > Default
1 Closed contact.
22
+EDW
Heater Break Alarm Threshold
Heater Break Alarm activation threshold
Word modbus 2022
LabSoftView:
0..55.0 ampères > Default: 0
E.g. : 20 = 20 amps
Modbus:
0..550 dixièmes d’ampères
E.g. : 200 = 20.0 amps
0 = Alarm disable
23
+EDG
Heater Break Alarm Delay
Heater Break Alarm activation delay
Word modbus 2023
LabSoftView:
0..60.00 seconds >
Default: 0
Modbus:
TFDPOET
24
FRRI
Cooling Fluid
Type of refrigerant uid for heating / cooling PID
Word modbus 2024
0 Air. > Default
1 Huile
2 Eau