User manual - ECOM0010 57
Modbus
address
Description
Read
Write
Reset
value
Parameter R/W EEPROM
Parameter R/W EEPROM
Parameter ** R/W EEPROM
Parameter R/W EEPROM
Parameter R/W EEPROM
* H.B.A. Heater Break Alarm
** Par. modied using serial addresses from 4001 to 4044
are saved in eeprom only after 10 seconds from the last
parameter writing.
8 Table of conguration parameters
1
VHQ
Sensor 1
Analogue input conguration / sensor selection (AI1)
Word modbus 2001
0 Tc-K 0..1000°C
1 Tc-J 0..740°C > Default
2 Tc-T 0..400°C
5D&¡$
2
RFD
Oset Calibration AI1
Value added/subtracted to the visualized process value
(normally used to correct ambient temperature value)
Word modbus 2002
LabSoftView:
-99.9..+99.9 degrees >
Default: 0
E.g. : 10 = 10 °C / °F
Modbus:
-999..+999 tenths of
degrees
E.g. : 10 = 1.0 °C / °F